Chapter 10
Using Remote I/O

10 – 19

CONTINUOUS N

BTR

BTW

ENABLE

ENABLE

BTR

BLOCK TRNSFR READ-

RACK

GROUP

MODULE

CONTROL BLOCK

DATA FILE

LENGTH

CONTINUOUS N

BTR

BTW

ENABLE

ENABLE

BTW

BLOCK TRNSFR WRITE

RACK

GROUP

MODULE

CONTROL BLOCK

DATA FILE

LENGTH

NOTE: The Block Transfer Read instruction is required if DL40 data is to be
returned to the PLC or if the Handshake Enable DIP switch is in the ON
position.

Triggering a Message (Block Transfer Write)

Message/Variable/Slave Run Mode – Block Transfer Write

Length

can be

3 to 13 words. If

Length

is set to 0, a default length of 13 will be used.

The DL40 always interprets the last word as a slave address. If more than
13 words are sent, the DL40 will interpret the thirteenth word as a slave
address and ignore the rest.

Note: Word 13 = 0 tells the DL40 to use the slave address selected as a
message attribute.

Message/Variable Run Mode – Block Transfer Write

Length

can be 2 to

12 words. If

Length

is set to 0, a default length of 12 will be used. If

more than 12 words are sent, the DL40 accepts the first 12 words and
ignores the rest.