Chapter 11
Installation and Wiring

11 – 10

When a personal computer is used to upload or download application
memory to or from the DL40’s RS–485 port, a Black Box RS–485 converter,
Model LD-485A-MP should be used. The link from the personal computer to
the converter is an RS–232 link. The following cable is recommended:

for an AT style computer, use an Allen–Bradley 2706-NC 15.

for an XT style computer, see Appendix C.

Connect from the converter to the DL40 as shown in Figure 11.10. The
converter should be configured as follows:

1. Remove cover and set the converter as a DCE device using the XWlA

jumper. This is a DIP shunt jumper.

2. Short TXA and RXA on TB1 of the converter. This should be connected

to J6, pin 5 of the DL40.

3. Short TXB and RXB on TB1 of the converter. This should be connected

to J6, pin 4 of the DL40.

4. Set switch W8 on the converter for full-duplex operation when

downloading or triggering messages via the RS–485 Port.

5. Set the RTS/CTS delay time to 5 milliseconds using jumper W9.

6. Set switch S2 to Unterminated position.

7. Replace cover.

8. Set Normal/Loopback switch on front cover to Normal.

Figure 11.10
Wiring the RS–485 Port when Port Use is Set to Programmer

RS-485 Port Set to
Programmer