10 - using remote i/o, Chapter objectives, Communication – Rockwell Automation 2706 DL40 HARDWARE USER MANUAL User Manual

Page 93: Using remote i/o

Advertising
background image

Chapter

10

Chapter 10
Using Remote I/O

Figure 10Table 10

10 – 1

Chapter 9

Using Remote I/O

This chapter discusses communication and compatibility considerations
related to using the DL40 Message Display with programmable controllers.
Topics also include the Remote I/O architecture and factors in calculating
rack size, as well as triggering messages.

The Remote I/O version of the DL40 Message Display communicates with
all Allen-Bradley programmable controllers that support the Remote I/O link.

These displays communicate with PLC controllers and Remote I/O scanners
and sub-scanners as if they were a Remote I/O rack. The displays contain all
the necessary electronics to connect directly to the Remote I/O cable that
originates from a PLC, scanner, or sub-scanner. These scanners have both
physical and logical specifications which are as follows:

Physical Specifications – The maximum number of separate Remote I/O
devices (I/O racks, drive systems, DL40s, etc.) the scanner can communicate
to.

Logical Specifications – The maximum number of racks the scanner can
address.

Note: Different scanners have different physical and logical specifications.
Please refer to Table 10.E (Remote I/O Configuration) for these
specifications.

To configure DL40s with the PLC controllers you need to know:

1. The appropriate PLC or scanner module. This is found in the next section,

Remote I/O Architecture.

2. The amount of I/O the DL40 uses for different applications.

3. The number of chassis (1771 I/O racks or DL40s) and the amount of rack

I/O addressing the scanner can accommodate.

Chapter Objectives

Communication

Advertising