Chapter 10
Using Remote I/O

10 – 24

Adding or Deleting Messages and/or Triggering a Priority Message
(Block Transfer Write)

Note: If Block Transfer Write

Length

is set to 0 in your PLC program, a

default length of 2 will be used.

WORD 1

17 16 15

14

Priority Message Number

Message Number

WORD 0

Add/Delete Bit

Block Transfer Write

File

Any rack size

Messages can be added or deleted while Priority Messages are being
triggered. If you want to trigger a Priority Message but do not want to change
the Message List, you must set

Message Number

(in word 1) to 0.

Return Message Number and ASCII Data for
Message Being Displayed and Length of Message List to PLC
(Block Transfer Read)

Note: If Block Transfer Read

Length

is set to 0 in the PLC program, the

DL40 will return 12 words.

WORD 1

17 16 15

14

Message Number

WORD 0

Enter Bit

Block Transfer Read File

Any rack size-2 to 12 Words

WORD 2

WORD 3

ASCII Character 1

Acknowledge Bit

Clock/Date Data Bit = 0

Diagnostic Code

ASCII Character 3

ASCII Character 2

ASCII Character 4

WORD 4

WORD 5

ASCII Character 7

ASCII Character 6

ASCII Character 8

ASCII Character 5

WORD 6

WORD 7

ASCII Character 11

ASCII Character 10

ASCII Character 12

ASCII Character 9

WORD 8

ASCII Character 13

ASCII Character 14

WORD 9

ASCII Character 15

ASCII Character 16

WORD 10

ASCII Character 17

ASCII Character 18

WORD 11

ASCII Character 19

ASCII Character 20

Length of Message List