Block transfer, Return clock or date data to plc – Rockwell Automation 2706 DL40 HARDWARE USER MANUAL User Manual

Page 115

Advertising
background image

Chapter 10
Using Remote I/O

10 – 23

Return Clock or Date Data to PLC

WORD 1

17 16 15

14

WORD 0

Input Image Table

WORD 2

WORD 3

Always Returned Empty

Acknowledge Bit

Clock/Date Data Bit

Diagnostic Code

WORD 4

WORD 5

WORD 6

Hour/Month

Handshake Bit

Full rack

1/2 rack

3/4 rack

WORD 7

Second/Year

Minute/Day

Always Returned Empty

Always Returned Empty

Always Returned Empty

Always Returned Empty

Always Returned Empty

Block Transfer

Note: If Block Transfer DIP Switch (Switch 2–4) is enabled, all functions
between the PLC and DL40 must be made by Block Transfer.

Important: The block transfer must be configured as non–continuous using
ladder logic consistent with the following:

CONTINUOUS N

BTR

BTW

ENABLE

ENABLE

BTR

BLOCK TRNSFR READ

RACK

GROUP

MODULE

CONTROL BLOCK

DATA FILE

LENGTH

CONTINUOUS N

BTR

BTW

ENABLE

ENABLE

BTW

BLOCK TRNSFR WRITE

RACK

GROUP

MODULE

CONTROL BLOCK

DATA FILE

LENGTH