L Leakage High - indicates that the measured leakage inductance is greater

than 0.35 pu. Possible causes are:
The inductance of long motor cables is increasing the apparent leakage

inductance of the motor. In this case, the measured leakage inductance
is probably correct.

The motor is very small (leakage inductance generally increases with

decreasing motor size).

Because of the design of the motor, this method of measuring leakage

inductance does not produce a valid result. Obtain the leakage
inductance from the motor data sheet, or if this is not possible, set the L
Total Leakage parameter to its default value of 0.20 pu.

Flux Speed Regulator (Induction Motors)

This method combines the auto-tuning of the Flux and Speed regulator in a
single step. It calculates parameters, Lm Rated (P#131), T Rotor (P#132) in
Motor Model Group and Total Inertia (P#82) in Speed Control group.

During this auto-tune step the motor will run at speed set in Autotune Spd Cmd.
The default setting is 30 Hz. Ensure the motor rotates during this auto-tune.
Verify motor rotation physically or by monitoring FlxFbk VoltModel (P#342).
Stall condition may calculate wrong tuning parameters. If it happens, ensure you
set the tuning parameters Lm Rated, T Rotor, and Total Inertia to default before
re-starting this tuning.

Flux Regulator

Three parameters determine tuning for the flux regulator in an induction motor:

FlxReg Bandwidth in Flux Control
Lm Rated in Motor Model
T Rotor in Motor Model

Set FlxReg Bandwidth to the default value of 10 r/s for almost all applications.
Lm Rated and T Rotor are usually unknown; measure them individually. Both of
these motor parameters change substantially with different operating conditions,
but the variations do not significantly affect the operation of the flux regulator.

IMPORTANT

For synchronous motors, please refer

Flux Speed Regulator (Synchronous

Motors) on page 106

.