Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

49

Commissioning the Drive Chapter 4

Refer to

Table 1 on page 46

to determine the appropriate snubber resistance value

for the current rating of the SGCT used.

If the resistor is found to be out of tolerance, refer to publication

7000-UM202_-

EN-P

for detailed instructions on replacing the snubber resistor assembly.

Snubber Capacitance (SGCT Device)

Turn the multimeter from the resistance to capacitance measurement mode.
Verify the snubber capacitor by measuring from the test point to the heat sink
adjacent to the right for standard rectifiers, or from heat sink to heat sink. For
SPS rectifiers, measure from the test point to pin 1 of the Phoenix connector that
plugs into J1 of the SPS board (disconnect the J1 connector from the SPS board
first).

Figure 34 - Snubber Capacitor Test

Heatsink

Heatsink

Snubber
Resistor

Snubber
Capacitor

Sharing Resistor

SGCT

Test Point

Measure capacitance
between heat sink
and test point (or
from heat sink to
heat sink)

Snubber test point