Chapter 4 Commissioning the Drive

Figure 81 - Sample waveforms: 20 deg phase shift between master and 2 slave bridges

Verify the phase shift is:

V2uv must be 0º
V3uv must be -20º
V4uv must be +20º

Harmonic Analysis (required
for PWM drives only)

Measure the harmonic (resonance) levels at the input to the drive. If you notice
considerable distortion in the waveforms, you MUST send those waveforms to
MV Support via e-mail at [email protected], and then call
519-740-4790 (option 1) to discuss the issue and action plan. After-hours, call
(519-503-0346) to talk with MV Tech Support Specialist. Outside North
America, call 1-440-646-3434 and request MV Tech Support.

Summary:

Close all drive input contactors. If the drive input contactor configuration

is set to NOT RUNNING, temporarily change it to ALL FAULTS.

Verify the drive is not running when capturing these waveforms.
Capture line voltage at ACB test point “V2uv” and line current at ACB

test point “I2u”.

Label the waveforms as “V2uv”, and “I2u”.
Save the worksheet as “Harmonics (Drive Not Running)”.

Table 5 - Oscilloscope Settings

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform
Label

Sheet Name

Chan. 1

10 ms/div.

Line Voltage

V2uv

V2uv

Harmonics (drive
not running)

Chan. 2

Line Current

I2u

V2vw