Commissioning the Drive Chapter 4

Load Test

After autotuning of the drive, run the motor on load and capture the following
waveforms at 50% load and at 100% load. If the system is not ready for 100% load
test, then capture the waveforms at the max load you are allowed to run the drive
at. Also, print variables at 50% and 100% load points. Before printing variables
make sure the drive Access Level is at SERVICE.

Capture line voltage & current waveforms at ACB test points “V2uv” &

“I2u”.

Label the waveforms as “V2uv” and “I2u”.
Capture motor voltage & current waveforms at ACB test points “Vuv” &

“Iu”

Label the waveforms as “Vuv” and “Iu”.
Save the worksheet as “Line and Load Voltage and Current Waveforms at

1048 rpm, 31 A”, for example.

Table 7 - Oscilloscope Settings

Sample Waveforms

Sample waveforms recorded on PWM drive running at full load (Ch1: Line
Voltage, Ch2 - Line Current, Ch3 - Motor Voltage, Ch4 - Motor Current)

Figure 85 - Sample waveform: PWM drive under full load condition

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform
Label

Sheet Name

Chan. 1

10ms/div.

Line Voltage

V2uv

V2uv

{see above]

Chan. 2

Line Current

I2u

I2u

Chan. 3

Motor Voltage

Vuv

Vuv

Chan. 4

Motor Current

Iu

Iu