Appendix A General Reference

Table 11 - PowerFlex Speed Regulation

Notes:

Speed regulation is based on a percentage of motor synchronous speed.
Encoder to be mounted on the AC machine
Operational 15V DC Power Supply mounted in drive to power the

encoder as a standard option with the encoder feed back card.

Customer is responsible for providing and mounting of encoder
Sleeve bearing motors require the encoder to have an axial movement

tolerance.

Recommended tachometers are shaft mounting type.
Magneto resistive models are more adaptable to harsh environments.
When installing, the encoder body and electronics must be isolated from

ground (options available from the encoder manufacturer to accomplish
this).

There are usually limits on encoder cable lengths. Ensure the maximum

length is suitable for the application.

Encoder

Frequency Output

<6 Hz

6...15 Hz

>15 Hz

Without Encoder

Not applicable

0.1%

0.1%

With Encoder

0.02%

0.01%

0.01%

With Encoder and HPTC
mode enabled

0.01%

0.01%

0.01%