Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

Chapter 4 Commissioning the Drive

Snubber Resistors

Snubber resistors connect in series with the snubber capacitors. Together they
form a simple RC snubber that connects across each thyristor (SCR or SGCT).
The snubber circuit reduces the dv/dt stress on the thyristors and reduces the
switching losses. The snubber resistors connect as sets of various wire-wound
resistors connected in parallel. The number of resistors in parallel depends on the
type of the thyristor and the configuration and frame size of the drive.

Snubber Capacitors

Snubber capacitors are connected in series with the snubber resistors. Together
they form a simple RC snubber that is connected across each thyristor (SGCT).
The purpose of the snubber circuit is to reduce the voltage stress (dv/dt and peak)
of the thyristor and to reduce the switching loss.

Sharing Resistors

Sharing resistors provides equal voltage sharing when using matched devices in
series. Please note, SGCT PowerCages for 2400V systems do not need matched
devices and have no sharing resistor.

SCR PowerCages always have sharing resistors even if matched devices are not
necessary. Sharing resistors in SCR PowerCages provide a diagnostic function.