Live synchronous transfer – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) Commissioning - ForGe Control User Manual

Page 120

Advertising
background image

120

Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

Chapter 4 Commissioning the Drive

Sample Waveforms

Synchronous Transfer Test to verify Sync Lead Angle (50Hz System); Ch1: Idc1
(yellow), Ch2: Vuv (blue), Ch3: Vuvs (red)

Figure 88 - Sample waveform: Synchronous transfer test

Live Synchronous Transfer

While performing a live synchronous transfer:

1.

Capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.

2.

Capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.

3.

Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.

4.

Save the worksheet as “Synch on Motor 01”, for example.

Table 10 - Oscilloscope Settings

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform
Label

Chan. 1

10ms/div.

DC Link Current

Idc1

Idc1

Chan. 2

Motor Voltage

Vuv

Vuv

Chan. 3

Bypass Line
Voltage

Vuvs

Vuvs