Commissioning the Drive Chapter 4
Sample Waveforms
Sample waveforms captured on ACB test points under Drive Not Running
Condition [Ch1: V2uv (red), Ch2: I2u (yellow)]
Figure 82 - Sample waveform: SCBL test points (drive not running)
DC Current Test
• Make sure the Diagnostic Trend has been setup and is armed.
• Run the DC Test with Idc Command Test (P119) set to 0.1pu. Increase
Idc Command Test from 0.1 to 0.3pu (for AFE drives) or from 0.1 to
0.7pu (for 18 Pulse drives) in steps of 0.1pu. At each step, verify DC link
current regulation by monitoring Idc Error (P323) and Alpha Line (P327).
• Capture DC link voltage waveform at ACB test point “Vdcr1” and DC
link current waveform at ACB test point “Idc1” at 0.3pu (for AFE drives)
or at 0.7pu (for 18 Pulse drives).
• Label the waveforms as “Vdcr1”, and “Idc1”.
• Save the worksheet as “DC Test @ 0.3pu” (for AFE drives) or “DC Test @
0.7pu” (for 18 Pulse drives).
Table 6 - Oscilloscope Settings
Oscilloscope
Time Base
Wave Form
Test-Point
Waveform
Label
Sheet Name
Chan. 1
2ms/div.
DC Link Voltage
Vdcr1
Vdcr1
DC Test
Chan. 2
DC Link Current
Idc1
Idc1