Commissioning the Drive Chapter 4

Sample Waveforms

Sample waveforms captured on ACB test points under Drive Not Running
Condition [Ch1: V2uv (red), Ch2: I2u (yellow)]

Figure 82 - Sample waveform: SCBL test points (drive not running)

DC Current Test

Make sure the Diagnostic Trend has been setup and is armed.
Run the DC Test with Idc Command Test (P119) set to 0.1pu. Increase

Idc Command Test from 0.1 to 0.3pu (for AFE drives) or from 0.1 to
0.7pu (for 18 Pulse drives) in steps of 0.1pu. At each step, verify DC link
current regulation by monitoring Idc Error (P323) and Alpha Line (P327).

Capture DC link voltage waveform at ACB test point “Vdcr1” and DC

link current waveform at ACB test point “Idc1” at 0.3pu (for AFE drives)
or at 0.7pu (for 18 Pulse drives).

Label the waveforms as “Vdcr1”, and “Idc1”.
Save the worksheet as “DC Test @ 0.3pu” (for AFE drives) or “DC Test @

0.7pu” (for 18 Pulse drives).

Table 6 - Oscilloscope Settings

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform
Label

Sheet Name

Chan. 1

2ms/div.

DC Link Voltage

Vdcr1

Vdcr1

DC Test

Chan. 2

DC Link Current

Idc1

Idc1