Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

123

Appendix

A

General Reference

Torque Requirements for
Threaded Fasteners

Unless otherwise specified, use the following values of torque in maintaining the
equipment.

Encoder Usage

When is an Encoder Required?

An encoder is required under the following conditions:

1.

When speed regulation accuracy must be between 0.01...0.02% of nominal
speed.

2.

When the zero speed breakaway torque needed is greater than 90% of
continuous running torque.

3.

When continuous running speed is greater than or equal to 0.1 Hz, but less
than 6 Hz.

4.

For minimizing restart times using the flying start capability in forward or
reverse direction.

5.

At any time when high performance torque or speed control mode
(HPTC) is enabled.

Diameter

Pitch

Material

Torque (N•m)

Torque (lb•ft)

M2.5

0.45

Steel

0.43

0.32

M4

0.70

Steel

1.8

1.3

M5

0.80

Steel

3.4

2.5

M6

1.00

Steel

6.0

4.4

M8

1.25

Steel

14

11

M10

1.50

Steel

29

21

M12

1.75

Steel

50

37

M14

2.00

Steel

81

60

1/4”

20

Steel S.A.E. 5

12

9.0

3/8”

16

Steel S.A.E. 2l

27

20