Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

71

Commissioning the Drive Chapter 4

5.

Select Operating Mode, and click Value to open the Operating Mode
dialog (

Figure 55

).

Figure 55 - Operating Mode window

6.

Choose Gate Test from the New Value pull-down menu and click OK.

The operating mode value changes to Gate Test (

Figure 56

).

Figure 56 - Gate Test Mode

SCR Firing Test

In normal operation, the SCR firing cards derive their power from a voltage
divider network that steps down the medium voltage to 20V DC maximum. As it
is necessary to perform this test while isolated from medium voltage, you need a
secondary power source for firing cards.

ATTENTION: Ensure that the drive is no longer running in test mode prior to
applying medium voltage to the drive line-up. Failure to do so may result in
equipment damage.