Sps board leds, Gating tests – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) Commissioning - ForGe Control User Manual

Page 69

Advertising
background image

Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

69

Commissioning the Drive Chapter 4

SPS Board LEDs

There is one green LED on each of the SPS boards labeled DS1. If the SPS board
is healthy, the corresponding LED will be illuminated (need 1, 2 or 3 test power
harnesses for 2kV/3...4 kV/6 kV drives, respectively). If any of the SPS board DS1
LEDs do not illuminate, the SPS board is defective. The output voltage should be
within 20 V, ± 2%.

Gating Tests

After testing the drive converters without Medium Voltage and verifying the
power supply output values, test the SCRs and SGCTs under low voltage control
power.

The following procedures describe the next level of device testing:

Gating Test Mode
SCR Firing Test
SGCT Firing Test

Test Points (SPS)

Expected Value

Measured Value

U1a

J2 1-2

+20V DC

U1b

J2 1-2

+20V DC

U1c

J2 1-2

+20V DC

U4a

J2 1-2

+20V DC

U4b

J2 1-2

+20V DC

U4c

J2 1-2

+20V DC

U3a

J2 1-2

+20V DC

U3b

J2 1-2

+20V DC

U3c

J2 1-2

+20V DC

U6a

J2 1-2

+20V DC

U6b

J2 1-2

+20V DC

U6c

J2 1-2

+20V DC

U5a

J2 1-2

+20V DC

U5b

J2 1-2

+20V DC

U5c

J2 1-2

+20V DC

U2a

J2 1-2

+20V DC

U2b

J2 1-2

+20V DC

U2c

J2 1-2

+20V DC

Advertising