Chapter 4 Commissioning the Drive
Diagnostics View
Captured data is shown in a table, with each column representing a trace
(
).
For binary data, select the desired capture point (row), and click the column
header to decode the value.
Figure 70 - View Sub Menu
The collection point at which the trigger condition occurred will be highlighted
in red.
Diagnostics Plot
The Plot tab (
) shows relationships and trends amongst the captured
data. Trace parameters which were selected on Setup tab are automatically
plotted when the Plot tab is selected.
To add or remove additional parameters from the plot:
• Select the desired parameter and click the X column header.
• Click Update to redraw the new plot.
Colors assigned to the parameter name correspond to the colors used in
the plot. All values in the plot are normalized.