Commissioning the Drive Chapter 4

18 Pulse Phasing Test

Prior to applying medium voltage and running the drive, it is important to verify
the phase rotation on the input of all 18 Pulse drives. The following tests do not
need to be performed on AFE rectifier drives unless they incorporate
synchronous transfer:

Line Terminal Resistance Measurements
Application of Medium Voltage Power

Compare the voltage feedback from all 9 test points in the ACB board

to ensure proper phasing.

Failure to perform the recommended tests will result in poor drive performance
and may result in drive converter damage.

Line Terminal Resistance Measurements

Measuring the resistance between the drive line cable terminals will quickly
identify if there is inter-wiring between the 0

º, +20º, and -20º bridges in the

isolation transformer.

Figure 63 - Line terminal designations