Silicon controlled rectifier powercages – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) Commissioning - ForGe Control User Manual

Page 51

Advertising
background image

Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

51

Commissioning the Drive Chapter 4

Silicon Controlled Rectifier
PowerCages

Figure 36

shows the snubber circuit.

Figure 37

shows the physical locations of the

same circuit.

Disconnect the 2-pole plug to the Gate Driver board marked TB1 on the circuit
board. Measure the resistance from the point of the plug that connects to the
point labeled V.SENSE on the Gate Driver board to the anode side heat sink. A
value of 80 kΩ indicates a good sharing resistor.

Figure 36 - Snubber Circuit for SCR Rectifier Module

T P

R s n-2

C s -1

R s h

A node

C s -2

S P G D B

Cathode

R s n-1

Advertising