Sample waveforms – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) Commissioning - ForGe Control User Manual

Page 113

Advertising
background image

Rockwell Automation Publication 7000-IN012B-EN-P - June 2014

113

Commissioning the Drive Chapter 4

Table 4 - Oscilloscope Settings

Use the same settings on the oscilloscope when capturing waveforms for the two
Slave bridges. If you are using a 2-channel oscilloscope, then first capture two
waveforms and move them onto a wavestar worksheet and after that capture the
remaining waveforms and move them onto the same wavestar worksheet.

Sample Waveforms

Sample Waveforms captured on ACB test points showing incoming line voltage
phasing [Ch1: V2uv (red), Ch2: V2vw (yellow), Ch3: V2wu (blue)]

Figure 80 - Sample waveforms: incoming line voltage phasing

Sample waveforms captured on ACB test points showing 20 deg Phase Shift
between Master and two Slave Bridges [Ch1-Master: V2uv (red), Ch2-Slave 1:
V3uv (yellow), Ch3-Slave 2: V4uv (blue)]:

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform
Label

Sheet Name

Chan. 1

5 ms/div.

2U Line Voltage

V2uv

V2uv

Input phasing

Chan. 2

2V Line Voltage

V2vw

V2vw

Chan. 3

2W Line Voltage

V2wu

V2wu