Commissioning the Drive Chapter 4

To see the true value of a captured point, even if it is not plotted:

Select the desired parameter from the list.
Click on the graph at the point where the desired value is sought.

The location is marked by a white marker and the true value is shown at the
bottom of the plot. Other parameter values can be read without moving
the marker point by selecting the desired parameter from the list. The red
marker shows the trigger point.

Figure 71 - Plot Sub Menu

When you finish programming these settings, the drive is ready to trend data at
the next fault. The next test required is to test phase rotation requires that
medium voltage be applied to the drive input.

Inspect the drive for debris and tools prior to energizing the drive.
Re-install all protective barriers.
Configure the drive to Normal operating mode (not System test).

True Value

Trace
Parameters