Sample waveforms recorded on 18 Pulse Drive running at 75% load (Ch1: Line
Voltage, Ch2 - Line Current, Ch3 - Motor Voltage, Ch4 - Motor Current)

Figure 86 - Sample waveform: 18 Pulse drive at 75% load capacity

Synchronous Transfer

When commissioning a drive employing synchronous transfer, capture and
submit the following waveforms with the commissioning package.

While measuring the bypass (BP) contactor closing time:

Capture 120V bypass close command from the BP Contactor Close

output ( J1-12) at the ACB (refer to electrical drawing for specific wire/
terminal number).

Capture the 9V signal across the bypass contactor vacuum bottles (refer to

the tech note PF7000_GEN-78 for details).

Label the waveforms as “BP_Close_Cmd” and “Actual_Closure”.
Save the worksheet as “Bypass Contactor Close Delay”.

Table 8 - Oscilloscope Settings

Oscilloscope

Time Base

Wave Form

Test-Point

Waveform Label

Chan. 1

25ms/div.

BP Contactor Close
Command

BP Contactor Close
Command

BP_Close_Cmd

Chan. 2

Actual Closure of BP

Across 2K-Ohm resistor
connected in series with 9V
battery

Actual_Closure