Commissioning the Drive Chapter 4

1.

Click the Display tab and select Feature Select from the Group Name
column.

The group parameters show in the right window.

2.

Select Operating Mode and click Value to open the Operating Mode
dialog (

Figure 55

).

3.

Select System Test from the New Value pulldown menu and click OK.

The Operating Mode Value changes to System Test (

Figure 59

).

Figure 59 - System Test Mode

Start/Stop Control Circuit

Once the drive is in System Test mode, ensure that the stop/start circuit functions
as desired. If necessary, review the electrical schematic drawings prior to
performing this test to better understand the control circuit.

Start the drive in local control while observing the system vacuum contactors or
customer supplied circuit breakers. If you must troubleshoot Rockwell
Automation medium voltage switchgear, refer to the following publications:

Publication

1500-UM055_-EN-P

, Medium Voltage Controller, Bulletin

1512B, Two-High Cabinet, 400 Amp • User Manual

Publication

1503-IN050_-EN-P

, OEM Starter Frame and Components •

Installation Manual

Publication

1502-UM050_-EN-P,

Medium Voltage Contactor, Bulletin

1502, 400 Amp (Series D) • User Manual

Publication

1502-UM052_-EN-P

, Medium Voltage Contactor, Bulletin

1502, 400 Amp (Series E) • User Manual

TIP

You can check the entire system without medium voltage. As long as all the
contactors have test power, you can start, stop, E-Stop, trigger faults, check
remote IO, check PLC inputs, and verify other functions.

Ensure that the drive is no longer running in system test mode

prior to applying medium voltage to the drive line-up. Failure

to do so may result in equipment damage.

ATTENTION: Ensure that the drive is no longer running in system test mode
prior to applying medium voltage to the drive line-up. Failure to do so may
result in equipment damage.