Verifying Hookups
99
Then, do the following:
1. In the Hookups page of the Configure Axis Use dialog box, select the
Drive Offset button. The controller tests for drift, and displays a
message box containing the cumulative drift.
2. Go to the drive and manually adjust the drive offset potentiometer, so
that the drive is as near to perfectly still as possible.
3. In GML Commander, select OK. The message box closes, and GML
Commander completes the two-step test by internally performing its
own drive offset compensation.
Note: The Drive Offset test applies only to a Velocity Drive Interface
(as set in the Servo page).
For IMC S Class 1394/1394 Turbo controllers, GML Commander
includes this test as part of the Motor/Encoder test.
Pulse Magnitude
Type the voltage to be generated for the battery box test, from 0.0 to 9.999
Volts.
Pulse Duration
Type the duration of the voltage pulse for the battery box test, from 1 to
999.0 seconds.
Pulse Type
Select the pulse type for the battery box test, from the drop-down menu.
!
ATTENTION: Failure to download can cause
uncontrolled motion when performing controller
diagnostic routines.