Rockwell Automation GMLC Reference Manual User Manual
Page 592

Publication GMLC-5.2 - November 1999
555
•
0 (false) if not.
When Axis_module_hard_fault_1394 = 1, Drive_hard_fault_1394 = 1.
The occurrence of one of the following underlying faults triggers the
Axis_module_hard_fault_1394:
•
Axis_bus_loss_fault_1394
•
Axis_Drive_over_temp_fault_1394
•
Axis_it_fault_1394
•
Axis_power_fault_1394
To clear this fault, you must clear the underlying fault with a Reset Fault
block, set to Reset 1394.
In the Tag Explorer, select both Axis System Variables and the desired
physical axis, then select Axis_module_hard_fault_1394 in the Tag
Window.
System Module Hard Fault 1394
System_module_hard_fault_1394 is a logical (Boolean) variable, with a
value of:
•
1 (true) if the 1394 system module has detected a fault condition, and
•
0 (false) if not.
When System_module_hard_fault_1394 = 1, Drive_hard_fault_1394 = 1.
The occurrence of one of the following underlying faults triggers the
System_module_hard_fault_1394:
•
System_bus_over_voltage_flt_1394
•
System_bus_under_voltage_flt_1394
•
System_control_power_fault_1394
•
System_ground_fault_1394