Each of the upper-tier, general fault variables along with all related lower
tier variables and fault codes are explained in the following pages.
Global Fault
Global_fault is an integer value representing the highest priority fault
currently active in the motion controller. Global faults include controller
memory faults as well as any faults on any axis. The table below displays
the global fault value alongside the corresponding message that appears in
a global fault field in the runtime display (if enabled).
System_smrt_pwr_shunt_timeout_fault_1394
0 (False) or 1 (True)
Fault
Value
Description
Runtime
Display
16
CNET_fault
CNET FLT
15
CPU_Utilization_Overrun_Fault
CPU FLT
14
Feedback_Device_Fault
FDB FLT
13
Flex_Fault
FLX FLT
12
SLC_Fault
CPU FLT
11
DH-485_General_Fault
DH FLT
10
RIO_Fault
RIO FLT
9
AxisLink _Timeout_Fault or
AxisLink_Failed on any virtual axis
AXL FLT
8
AxisLink_General_Fault
AXL FLT
7
Setup_Data_Memory_Fault
MEM FLT
6
Application_Program_Memory_Fault
PRG FLT
5
Drive_Fault on any axis
DRV FLT
4
Position_Error_Fault on any axis
ERR FLT
3
Hardware_Overtravel_Fault on any axis
HRD LIM
Variable
Units