On dh-485 status – Rockwell Automation GMLC Reference Manual User Manual
Page 431

Publication GMLC-5.2 - November 1999
394
DH-485 Blocks
With binary files, each element contains 16 bits—or sub-elements—but
the entire word containing the desired bit is transferred. A maximum of
1,920 bits may be represented in 240 data bytes.
See Allen-Bradley Data Highway/Data Highway Plus
™
/DH-485
Communication Protocol and Command Set Reference Manual
(publication 1770-6.5.16), for more information on the Protected Typed
Logical Write with Three Address Fields command.
On DH-485 Status
Use the On DH-485 Status block to:
•
Evaluate the status of DH-485 communications.
•
Pause the program until the specified DH-485 status condition is true.
The On DH-485 Status block resides on the DH-485 Toolbar.
See Using the DH-485 Option chapter in this manual for information on
configuring DH-485 operation.
DH-485 Value Block
DH-485 Command Data Bytes
GML Commander
File Type
Data Bytes
per Element
Maximum Elements per
GML Block
Binary
2 (16 bits)
120
Integer
2
120
Floating
4
60
ASCII
1
240
BCD
2
120
IntFloat
4
60