Configuring the UDC Module, Regulator Type, and Parameters

2-5

AC Line Frequency (Hz) (Range: 25, 50, or 60, +/- 2%)

The AC line frequency parameter is the nominal frequency being supplied to the
rectifier. There is no default value. You must select one of the three values from the
list.

Power Module

Part Number

The screen displays a list of the supported SB3000 Power Modules. Selection is
made based upon the current rating of the Power Module being configured. The
current ratings displayed are the rated RMS currents with no overload and 40° C
ambient temperature. The Power Module may be selected by part number or by the
corresponding wiring diagram number. There is no default selection. A Power
Module must be chosen from the list.

Current Limit (Amps RMS)

The current limit parameter will automatically default to the Power Module rated
amps. The value may be changed to any number less than the rated value.

Motor Data

Rated Motor Voltage (Volts RMS) (208V to 575V)

Enter the rated RMS voltage of the motor(s) being controlled by the load inverter.
There is no default value. The value entered must be greater than the AC Line
Voltage parameter. A warning will be generated if this condition is not met.

Table 2.2 – Supported SB3000 Power Modules

Current Rating

Part Number

Wiring Diagram

445 Amps

101165-190S (445A @ 4KHz)

W/D 30495-11 (445A @ 4KHz)

890 Amps

101165-190T (890A @ 4KHz)

W/D 30495-12 (890A @ 4KHz)

1335 Amps

101165-190V (1335A @ 4KHz)

W/D 30495-13 (1335A @ 4KHz)