SB3000 Local Tunable Variables

B-1

A

PPENDIX

B

SB3000 Local Tunable

Variables

C_E6

%

Capacitance

The value in this variable selects the
capacitance connected to the bus. The value is
scaled in microfarads.

Units:

µF

Default Value:

32400

Low Limit:

32400

High Limit:

97200

Step:

1

For a single power unit, assign a value of 32400. For two parallel power units,
64800. For three parallel power units, 97200.

GIT_E1%

Ground Current Threshold

A drive warning is generated (register 203/
1203, bit 2) if the ground current in the rectifier
goes above the value stored in this variable.
The value is scaled in amps times 10; i.e., 100
represents 10.0 amps.

Units:

Amps * 10

Default Value:

100

Low Limit:

10

High Limit:

2000

Step:

1

This value should be set above the value in the ground current feedback register
(208/1208) after the drive is operational.

IST_E1%

Current Sharing Warning Threshold

A drive warning is generated (register 203/
1203, bit 6) if the
bus current is less than the value stored in this
tunable variable. The value is scaled in amps
times 10; i.e., 600 represents 60.0 amps.

Units:

Amps * 10

Default Value:

600

Low Limit:

10

High Limit:

2000

Step:

1

This variable should be left at the default value if the rectifier has only a single power
unit.