Rockwell Automation SB3000 Configuration and Programming User Manual

Page 39

Advertising
background image

Configuring the UDC Module’s Registers

3-21

Voltage Reference Register

102/1102

The value in the Voltage Reference register is the desired DC bus
voltage. This value is the main input into the voltage loop on the PMI
Processor. The loop is enabled in register 100/1100, bit 0.

Sug. Var. Name:

VDC_REF%

Units:

Volts

Range:

See text

Access:

Read/Write

The minimum value is 1.414 times the RMS value of the AC line voltage plus 10%. The maximum value is
875V. If the value is outside this range, register 203/1203, bit 4 (WRN_RIL@) will be set.

Power Factor Current Reference Register

103/1103

The value in this register is the reference to the leading power factor
logic in the voltage regulator. If there is extra leading power factor
capacity, the SB3000 Rectifier can compensate for other machines
on the AC line that produce lagging power factors.

Sug. Var. Name:

IPF_REF%

Units:

RMS Amps

10

Range: Limited

by

rectifier capacity

Access:

Read/Write

This value selects the minimum RMS current that will be commanded independent of load. A value of 0
disables the power factor correction. The maximum current that can be commanded is a function of input
voltage, load requirements, and rectifier capacity. If the DC bus current is high, the reactive current will be
limited and register 203/1203, bit 3 will be set.

The value is entered in RMS Amps times 10. For example, 60.0 amps is entered as 600.

Refer also to the description of VAR feedback register 211/1211. The VAR Feedback register contains the
VARS (volt-amperes reactive) produced by the Rectifier in response to the reference in register 103/1103.

Test Code Register

105/1105

The value entered in this register is used as data for the built-in
bridge test procedures commanded by the Drive Control register
(100/1100). See Appendix G for detailed information on performing
the bridge test.

Sug. Var. Name:

TST_CODE%

Units:

See text

Range:

N/A

Access:

Read/Write

PMI D/A Output Register

106/1106

The value in the PMI D/A Output register is used to pass a variable in
the UDC to the PMI Processor to be displayed on one of the four PMI
meter ports. See section 3.7.2.

Sug. Var. Name:

PMI_DA%

Units:

See text

Range:

See text

Access:

Read/Write

This register can be used to display any variable in the AutoMax system as long as it is a 16-bit integer.
Double-integer or floating point values cannot be displayed on the PMI Processor’s D/A meter ports. The
desired value must be copied into this register by an application task. The value in the register is transmitted
to the PMI Regulator at the end of every scan.