Rockwell Automation SB3000 Configuration and Programming User Manual

Page 41

Advertising
background image

Configuring the UDC Module’s Registers

3-23

Drive Status Register (Continued)

200/1200

Power Factor Current In Limit

Bit 3

The Power Factor Current in Limit bit is set if
the power factor current is being limited by
the PMI to keep the current minor loop from
saturating.

Hex Value:

0008H

Sug. Var. Name:

IPF_LMT@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Line Synchronized

Bit 7

The Line Synchronized bit is set when the
PMI Processor is synchronized to the AC
line. This bit is valid when the Rectifier has
input power, whether the voltage control
loop is on or not.

Hex Value:

0080H

Sug. Var. Name:

LIN_SYN@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

If this bit is not on when VDC_RUN@ is commanded, an Interlock failure will occur.
See the description of the IC_SYN@ bit (register 205/1205, bit 6).

Fault Detected

Bit 8

The Fault Detected bit is set if any fault is
detected in the Rectifier. This bit is reset by
bit 8 of register 100/1100.

Hex Value:

0100H

Sug. Var. Name:

FLT@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

See the description of the Drive Fault register (202/1202) for more information.

Warning Detected

Bit 9

The Warning Detected bit is set if any
warning is detected in the Rectifier. This bit
is reset by bit 9 of register 100/1100.

Hex Value:

0200H

Sug. Var. Name:

WRN@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

See the description of the Drive Warning register (203/1203) for more information.

Rail Data Ready

Bit 13

The Rail Data Ready bit is set when the PMI
Processor rail data is valid.

Hex Value:

2000H

Sug. Var. Name:

RAIL_OK@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Advertising