B-2

SB3000 Drive Configuration and Programming

L_E6% Inductance

The value stored in this variable sets the
inductance of the Power Module. The value is
scaled in microhenries.

Units:

µH

Default Value:

500

Low Limit:

167

High Limit:

500

Step:

1

For a single power unit, assign a value of 500. For two parallel power units, 250. For
three parallel units, 167.

OVT_E0%

Overvoltage Warning Threshold

A warning is generated (register 203/1203,
bit 0) if the DC bus voltage exceeds the value
stored in this variable. The value is scaled in
volts.

Units:

Volts

Default Value:

850

Low Limit:

600

High Limit:

925

Step:

1

This value should be set above the normal operating voltage (displayed in the DC
Bus Voltage Feedback register, 206/1206).

UVT_E0%

Undervoltage Warning Threshold

A drive warning is generated (register 203/
1203, bit 1) if DC bus voltage is less than the
value stored in this variable. The value is scaled
in volts.

Units:

Volts

Default Value:

750

Low Limit:

600

High Limit:

925

Step:

1

VDC_A%

Voltage Loop Damping Factor

The value in this variable selects the desired
response of the voltage loop. This value is used
by the PMI Processor to determine the integral
gain (Ki) of the voltage loop:
Ki = VDC_WCO% ÷ VDC_A%

Units:

None

Default Value:

120

Low Limit:

40

High Limit:

200

Step:

1

The higher the value, the smaller the integral gain and the overshoot in the voltage
loop. The lower the value, the larger the integral gain and the overshoot in the
voltage loop. Ideally, the value should be set equal to 0.4 * VDC_WCO%.

VDC_FF%

Voltage Loop Feed Forward

The value in this variable selects the feed
forward gain in the voltage loop. This value
should normally be set to 1000.

Units:

None

Default Value:

1000

Low Limit:

0

High Limit:

1400

Step:

1