SB3000 Drive Configuration and Programming

Table 3.5 – Fault Register and Check Bit Fault Counter Register

Usage for a Digital I/O Rail or 4-Input Analog Rail Module

Drive A

Registers

Drive B

Registers

Description

4

16

Port 0 Fault Register

10

22

Port 1 Fault Register

Bit 0: Analog Channel 0 Input Over-Range

Bit 1: Analog Channel 0 Input Under-Range

Bit 2: Analog Channel 1 Input Over-Range

Bit 3: Analog Channel 1 Input Under-Range

Bit 4: Analog Channel 2 Input Over-Range

Bit 5: Analog Channel 2 Input Under-Range

Bit 6: Analog Channel 3 Input Over-Range

Bit 7: Analog Channel 3 Input Under-Range

Bit 8: No device plugged into a configured port

Bit 9: Bad ID code: device other than rail plugged into port

Bit 10: Bad rail communication check bits received

Bit 11: PMI interface not ready

5

17

Port 0 Check Bit Fault Counter Register

11

23

Port 1 Check Bit Fault Counter Register

These registers can be reset by setting bit 9 of the Drive
Control register (100/1100)

Table 3.6 – Fault Register and Check Bit Fault Counter Register

Usage for a 2-Output/2-Input Analog Rail Module

Drive A

Registers

Drive B

Registers

Description

4

16

Port 0 Fault Register

10

22

Port 1 Fault Register

Bit 4: Analog Channel 2 Input Over-Range

Bit 5: Analog Channel 2 Input Under-Range

Bit 6: Analog Channel 3 Input Over-Range

Bit 7: Analog Channel 3 Input Under-Range

Bit 8: No device plugged into a configured port

Bit 9: Bad ID code: device other than rail plugged into port

Bit 10: Bad rail communication check bits received

Bit 11: PMI interface is not ready

5

17

Port 0 Check Bit Fault Counter Register

11

23

Port 1 Check Bit Fault Counter Register

The register can be reset by setting bit 9 of the Drive
Control register (100/1100)