SB3000 Local Tunable Variables

B-3

VDC_KD%

Voltage Loop Derivative Gain

The value in this variable selects the voltage
loop derivative gain. This value should normally
be set to 0.

Units:

None

Default Value:

0

Low Limit:

0

High Limit:

400

Step:

1

VDC_WCO%

Voltage Loop Crossover Frequency

The value in this variable selects the desired
response of the voltage loop. The higher the
value, the more quickly the rectifier responds to
a change in voltage reference. The value is
entered in radians/second.

Units:

rads/sec

Default Value:

300

Low Limit:

100

High Limit:

500

Step:

1

The factory default value of 300 rad/sec is the recommended value. System
operation should be tested at this level before any adjustments are made. Note that
if this value is adjusted too high, the voltage loop will become unstable.