Configuring the UDC Module’s Registers

3-19

Drive Control Register (Continued)

100/1100

Enable Parallel Power Module B

Bit 11

This bit is set to enable the bridge test in the
second power module in a parallel power
module configuration. Bit 2 in this register
must be set first and the pre-charge
contactor must close before this bit can be
set.

Hex Value:

0800H

Sug. Var. Name:

PPM_ENB@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

See the description of bit 2 above and G for more information about performing the
bridge test.

Enable Parallel Power Module C

Bit 12

This bit is set to enable the bridge test in the
third power module in a parallel power
module configuration. Bit 2 in this register
must be set first and the pre-charge
contactor must close before this bit can be
set.

Hex Value:

1000H

Sug. Var. Name:

PPM_ENC@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

See the description of bit 2 above and G for more information about performing the
bridge test.

UDC Task Running

Bit 15

The UDC Task Running bit is a status bit
that indicates that the UDC task is running.
This bit is used by the PMI Regulator to
prevent the minor loop from running if the
UDC task is not running.

Hex Value:

8000H

Sug. Var. Name:

UDC_RUN@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

This bit must NOT be written to by the user. This is a status bit that must only be
written to by the operating system.