Rockwell Automation SB3000 Configuration and Programming User Manual

Page 48

Advertising
background image

3-30

SB3000 Drive Configuration and Programming

Drive Warning Register

203/1203

The warnings indicated by the Drive Warning register cause no action by themselves. Any resulting action is
determined by the application task. The user must ensure that the AutoMax application task monitors
register 203/1203 and takes appropriate action if any of these conditions occurs. If a warning condition is
detected, the corresponding bit is latched until the Warning Reset bit (bit 9) of the Drive Control register
(register 100/1100) is set.

DC Bus Overvoltage Warning

Bit 0

The DC Bus Overvoltage Warning bit is set
if the DC bus voltage rises above the
overvoltage threshold value stored in local
tunable OVT_E0%.

Hex Value:

0001H

Sug. Var. Name:

WRN_OV@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

DC Bus Undervoltage Warning

Bit 1

The DC Bus Undervoltage Warning bit is set
if the DC bus voltage drops below the
undervoltage threshold stored in local
tunable UVT_E0%.

Hex Value:

0002H

Sug. Var. Name:

WRN_UV@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Ground Current Warning

Bit 2

The Ground Current Warning bit is set if
ground current exceeds the ground current
level stored in local tunable GIT_E1%.

Hex Value:

0004H

Sug. Var. Name:

WRN_GND@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Phase Loss Warning

Bit 3

The Phase Loss Warning bit is set if a phase
loss occurs in the AC line. Note that the
phase loss diagnostic cannot detect a phase
loss if there is no load current.

Hex Value:

0008H

Sug. Var. Name:

WRN_PL@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A