Configuring the UDC Module’s Registers

3-7

Table 3.3 – Rail I/O Port Registers

Drive A

Registers

Drive B

Registers

Port and Channel

Rail Type and Signal

4 Output

1

4 Input

2

2 Input

3

2 Output

Digital

I/O

4

0

12

Port 0 - Channel 0

Output 0

Input 0

Output 0

Digital

1

13

Port 0 - Channel 1

Output 1

Input 1

Output 1

N/A

2

14

Port 0 - Channel 2

Output 2

Input 2

Input 2

N/A

3

15

Port 0 - Channel 3

Output 3

Input 3

Input 3

N/A

4

16

Port 0 - Fault Register (Tables 3.4 - 3.6)

5

17

Port 0 - Check Bit Fault Count Register (Tables 3.4 - 3.6)

6

18

Port 1 - Channel 0

Output 0

Input 0

Output 0

Digital

7

19

Port 1 - Channel 1

Output 1

Input 1

Output 1

N/A

8

20

Port 1 - Channel 2

Output 2

Input 2

Input 2

N/A

9

21

Port 1 - Channel 3

Output 3

Input 3

Input 3

N/A

10

22

Port 1 - Fault Register (Tables 3.4 - 3.6)

11

23

Port 1 - Check Bit Fault Count Register (Tables 3.4 - 3.6)

1. 4-Output Analog Rail Module (M/N 61C365, 61C366)
2. 4-Input Analog Rail Module (M/N 61C345, 61C346)
3. 2-Output/2-Input Analog Rail Module (M/N 61C350, 61C351)
4. Digital I/O Rail (M/N 45C1), Thumbwheel Switch Input Module (M/N 45C630), or LED Output Module (M/N 45C631

Table 3.4 – Fault Register and Check Bit Fault Counter Register

Usage for a Digital I/O Rail or 4-Output Analog Rail Module

Drive A

Registers

Drive B

Registers

Description

4

16

Port 0 Fault Register

10

22

Port 1 Fault Register

Bit 8: No device plugged into a configured port

Bit 9: Bad ID code: device other than a rail plugged into the
port

Bit 10: Bad rail communication check bits received

Bit 11: PMI interface is not ready

5

17

Port 0 Check Bit Fault Counter Register

11

23

Port 1 Check Bit Fault Counter Register

These registers can be reset by setting bit 9 of the Drive
Control register (100/1100)