SB3000 Drive Register Reference

REGISTER MAP

Registers

Function

0-23

Analog ch. 0 input over-range

24-79

System Use Only

1

80-89

UDC/PMI comm. status registers for drive A

90-99

System Use Only

1

100-106

Command registers for drive A

107-199

System Use Only

1

200-222

Feedback registers for drive A

223-299

System Use Only

1

300-599

Application registers updated every scan

for drives A and B

600-999

System Use Only

1

1000

UDC module test switch register

1001-1017

UDC module meter port setup registers

1018-1079

System Use Only

1

1080-1089

UDC/PMI comm. status registers for drive B

1090-1099

System Use Only

1

1100-1106

Command registers for drive B

1107-1199

System Use Only

1

1200-1221

Feedback registers for drive B

1222-1299

System Use Only

1

1300-1599

Application registers updated every scan
for drives A and B

1600-1999

System Use Only

1

2000-2010

Interrupt Status and Control registers for
drives A and B

2011-2047

System Use Only

1

(1) These registers cannot be written to by

the user.

REGISTER/BIT DESCRIPTIONS

RAIL I/O PORT REGISTERS

A/B

0 / 12

PMI port 0, channel 0

1 / 13

PMI port 0, channel 1

2 / 14

PMI port 0, channel 2

3 / 15

PMI port 0, channel 3

4 / 16

PMI port 0 faults (see below)

5 / 17

PMI port 0 check bit fault counter

6 / 18

PMI port 1, channel 0

7 / 19

PMI port 1, channel 1

8 / 20

PMI port 1, channel 2

9 / 21

PMI port 1, channel 3

10 / 22

PMI port 1 faults (see below)

11 / 23

PMI port 1 check bit fault counter

Rail Fault Bits

0 Analog ch. 0 input over-range
1 Analog ch. 0 input under-range
2 Analog ch. 1 input over-range
3 Analog ch. 1 input under-range
4 Analog ch. 2 input over-range
5 Analog ch. 2 input under-range
6 Analog ch. 3 input over-range
7 Analog ch. 3 input under-range
8 No device plugged into configured port
9 Bad ID code
10 Bad rail comm. check bits received
11 PMI Processor interface not ready

UDC-PMI COMMUNICATION STATUS

A/B

80 /1080 UDC Module port status

Bit
0 Invalid rcr interrupt
1 No end of frame status
2 CRC/framing error
3 Overrun error
4 DMA format error
5 Transmitter underrun
6 CCLK comm sync error
7 Loopback data error
8 Missed gains
9 Multiplexed data verification error
10 No matching PMI OS
11 Invalid PMI OS header
12 Incompatible PMI H/W

81 /1081 UDC module good msg. recvd. count
82 /1082 UDC module CRC error count
83 /1083 UDC module format error count

84 /1084 PMI port status

Bit
0 Invalid rcr interrupt
1 No end of frame status
2 CRC/framing error
3 Overrun error
4 DMA format error
5 Transmitter underrun
6 CCLK comm sync error
8 UDC CCLK comm sync error
9 Multiplexed data verification error
12 Invalid PMI start OS address
13 Insuff. PMI memory to load PMI OS
14 Invalid PMI load address
15 PMI OS overflow

85 /1085 PMI good msg. recvd. count
86 /1086 PMI CRC error count
87 /1087 PMI format error count
88 /1088 Comm/link status
89 /1089 UDC transmitted msg. count

COMMAND REGISTERS

A/B

100/1100Drive Control

Bit
0 Enable minor loop

VDC_RUN@

2 Enable bridge test

BRG_TST@

8 Fault reset

FLT_RST@

9 Warning reset

WRN_RST@

10 Enable parallel PU A

PPM_EN1@

11 Enable parallel PU B

PPM_EN2@

12 Enable parallel PU C

PPM_EN3@

15 UDC task running (status)*

UDC_RUN@

101/1101I/O Control

Bit
2 External fault LED

EXT_FLT@

4 Auxiliary output

AUX_OUT@

15 UDC port loopback test

UDC_LB@

102/1102 Voltage reference

VDC_REF%

103/1103 Power factor current ref

IPF_REF%

105/1105 Test code

TST_CODE%

106/1106 PMI D/A output

PMI_DA%

FEEDBACK REGISTERS

A/B

200/1200 Drive status

Bit
0 Voltage loop on

VDC_ON@

1 Voltage loop standby

VDC_SB@

2 In current limit

IN_LMT@

3 Power factor current in limit

IPF_LMT@

7 Line synchronized

LIN_SYN@

8 Fault detected

FLT@

9 Warning detected

WRN@

13 Rail data ready

RAIL_OK@

14 CCLK synchronized

CCLK_OK@

15 PMI OS loaded

PMI_OK@

201/1201 I/O status

Bit
0 Run permissive input

RPI@

1 115 VAC auxiliary input 1

AUX_IN1@

2 115 VAC auxiliary input 2

AUX_IN2@

3 115 VAC auxiliary input 3

AUX_IN3@

4 115 VAC auxiliary input 4

AUX_IN4@

5 115 VAC auxiliary input 5

AUX_IN5@

12 Pre-charge feedback

CHG_FB@

202/1202 Drive fault

Bit
0 DC Bus overvoltage

FLT_OV@

1 DC bus overcurrent

FLT_DCI@

3 Instantaneous overcurrent

FLT_IOC@

4 LPI module fault

FLT_LPI@

5 GDI module fault

FLT_GDI@

6 Charge fault

FLT_CHG@

7 Overtemperature fault

FLT_OT@

10 Power loss fault

FLT_PWR@

11 Power technology fault

FLT_PTM@

12 PMI power supply fault

FLT_PS@

13 PMI read write fault

FLT_RW@

14 UDC run fault

FLT_RUN@

15 PMI communication lost

FLT_COM@

203/1203Drive warning

Bit
0 DC bus overvoltage

WRN_OV%

1 DC bus overcurrent

WRN_UV%

2 Ground current warning

WRN_GND%

3 Phase lost

WRN_PL%

4 Reference in limit

WRN_RIL%

6 Load sharing warning

WRN_SHR%

7 Overtemperature warning

WRN_OT%

8 Bad gain data

WRN_BGD%

9 Power module overload

WRN_OL%

10 Power loss

WRN_PWR%

12 PMI fan loss

WRN_FAN%

13 Rail communication error

WRN_RAL%

14 CCLK not synchronized

WRN_CLK%

15 PMI communication error

WRN_COM%

Advertising