Configuring the UDC Module’s Registers

3-31

Drive Warning Register (Continued)

203/1203

Reference In Limit Warning

Bit 4

The Reference in Limit Warning bit is set if
the VDC reference (register 102/1102).is
less than the minimum or greater than the
maximum allowed, where:

Minimum = 1.1 * 1.414 * AC line VRMS
Maximum = 875 volts

Hex Value:

0010H

Sug. Var. Name:

WRN_RIL@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

In Bridge Test mode, this bit is used by the bridge test to indicate an illegal test
code. Refer to the Bridge Test Enable bit (register 100/1100, bit 2) and to
Appendix G for additional information on the bridge test.

Load Sharing Warning

Bit 6

The Load Sharing Warning is set if a
problem occurs with current sharing
between parallel power modules.

Hex Value:

0040H

Sug. Var. Name:

WRN_SHR@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Bits 13, 14, or 15 in registers 204/1204, 220/1220, or 221/1221 will be set to indicate
the phase and the power module affected. Refer to the descriptions of these
registers for details.

Overtemperature Warning

Bit 7

The Overtemperature Warning bit is set if
the warning level thermal switch in the
power module opens.

Hex Value:

0080H

Sug. Var. Name:

WRN_OT@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

If power modules are connected in parallel, bit 12 is set in register 204/1204,
220/1220, or 221/1221 to indicate which power module is affected.

Bad Gain Data Warning

Bit 8

The Bad Gain warning bit is set if a tunable
variable is changed to an illegal value while
the UDC task is running. The value will be
restored to its previous valid value by the
PMI Processor.

Hex Value:

0100H

Sug. Var. Name:

WRN_BGD@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

For a description of the tunable variables, refer to Appendix B.