Rockwell Automation SB3000 Configuration and Programming User Manual

Page 45

Advertising
background image

Configuring the UDC Module’s Registers

3-27

Drive Fault Register (Continued)

202/1202

DC Bus Overcurrent Fault

Bit 1

The DC Bus Overcurrent Fault bit is set if
DC bus current exceeds 125% of the
Rectifier’s rated DC bus current.

Hex Value:

0002H

Sug. Var. Name:

FLT_DCI@

Access:

Read only

UDC Error Code:

1020

LED:

P.M. FLT

Instantaneous Overcurrent Fault

Bit 3

The Instantaneous Overcurrent Fault bit is
set if a power device overcurrent or
shoot-through fault occurs.

Hex Value:

0008H

Sug. Var. Name:

FLT_IOC@

Access:

Read only

UDC Error Code:

1017

LED:

P.M. FLT

Power Device Status registers 204/1204, 220/1220, and 221/1221 indicate faults in
Power Modules A, B, or C, respectively. If a single power module is used, only
register 204/1204 is valid.

Bits 0 - 5 in the appropriate status register are set to indicate which power devices
produced the fault. In the event of a shoot-through fault, bit 6 is set as well. Refer the
descriptions of these registers for further information.

Local Power Interface Fault

Bit 4

The Local Power Interface fault bit is set if
the power supply for the LPI module is not
operating within tolerance.

Hex Value:

0010H

Sug. Var. Name:

FLT_LPI@

Access:

Read only

UDC Error Code:

1022

LED:

P.M. FLT

Gate Driver Interface Fault

Bit 5

The Gate Driver Interface Fault bit is set if
the power supply on the Gate Driver
Interface (GDI) module is not operating
within tolerance.

Hex Value:

0020H

Sug. Var. Name:

FLT_GDI@

Access:

Read only

UDC Error Code:

1023

LED:

OK on GDI

module

If power modules are connected in parallel, bit 7 in register 204/1204, 220/1220, or
221/1221 is set to indicate which GDI module is affected.