Configuring the UDC Module’s Registers

3-47

Run Time AC Power Technology Module Faults (Continued)

Charge Fault Diagnostics

Diagnostic Fault Code Register (Continued)

222/1222

Code

Fault

Description/Action

22

A/D interrupt overrun

An interrupt from the ACPTM was
detected before the previous interrupt
was processed.

Replace the ACPTM, PMI rack, and/or
Power Supply.

23

Gate power test 1 fault

Gate power is on when the MCR is off
and Gate Enable is on.

Replace the ACPTM.

24

Gate power test 2 fault

Gate Power is on when MCR is off and
Gate Enable is on.

Replace the Resolver Interface.

25

Gate power test 3 fault

Gate power is on when the MCR is off
and Gate Enable is on.

Replace the ACPTM.

26

Gate power loss

Gate Power is off when MCR is on and
Gate Enable is on. This test is done on a
timed basis whenever the drive is on.

Replace the ACPTM.

Code

Fault

Description

100

Pre-charge closed

The pre-charge is closed when
commanded to be open.

101

Pre-charge did not close

The pre-charge did not close when
commanded.

102

Pre-charge opened (SW)

Software has detected that the
pre-charge opened when commanded
to be closed.

103

Pre-charge did not open

The pre-charge did not open when
commanded.

104

Pre-charge opened (ACPTM)

The AC Power Technology module
detected that the pre-charge opened
while in run.

105

Pre-charge Opened (GDI)

The Gate Driver Interface module
detected that the pre-charge opened
while in run.