Interlogix NX-6V2 Rev C Installation Manual User Manual

Page 26

Advertising
background image

Chapter 2: Reporting codes

22

NX-6V2 Control Panel Installation Manual

• If you want dual or split reporting and the split is based on the event type

(alarm, open/close, etc.), use only those events that are reported to phone 2.

• If you don’t want events reported to phone 2, program 0 in Location 10.

Segment 1

1. Alarms and alarm restores.
2. Opening and closings.
3. Zone bypass and bypass restore.
4. Zone trouble and trouble restores.
5. Power fail, low battery, power restore, and low battery restore.
6. Bell cut, telephone line cut, bell cut restore, telephone line restore.
7. Test reports.
8. Start and end programming, download complete.

Segment 2

1. Zone and box tamper and tamper restore.
2. Auxiliary power overcurrent and restore.
3. Sensor missing and restore.
4. Sensor low battery and restore.
5. Expander trouble and restore.
6. Fail to communicate.
7. Zone activity monitor.
8. Reserved.

Location 11 - Phone 2 partitions reported

Location 11 has one segment of feature selection data. Use this location to
program when events are to be reported to a phone number are based upon the
partition (1 or 2) regardless of the event. Enter 1 for partition 1 or enter 2 for
partition 2. If this location is used, Location 10 should be programmed as 0.

Location 12 - Phone 3

Location 12 has 20 segments of numerical data. Use this location to program
phone 3. The default for each segment is 14.

• To program a delay of 4 seconds, enter 13 in the appropriate segment.
• To program tone dialing, enter 15 in the segment where tone dialing begins.
• If the entire number is tone dialing, enter 15 in the first segment.
• Enter 11 for a *, and 12 for a #.
• Enter 14 to indicate the end of the phone number.

Caution:

A call-waiting cancel on a non call-waiting line prevents successful

connection to the central station.

Advertising