Chapter 2: Reporting codes

30

NX-6V2 Control Panel Installation Manual

Zone type

Description

21. Gas detection

Creates an instant alarm regardless of the armed state of the control
panel. It displays on the keypad and activates the keypad sounder.

22. Low temperature
detection

Creates an instant silent alarm regardless of the armed state of the
control panel. It displays on the keypad and activates the keypad
sounder.

23. High temperature
detection

Creates an instant silent alarm regardless of the armed state of the
control panel. It displays on the keypad and activates the keypad
sounder.

24. Manual fire

Illuminates the Fire LED and sounds the temporal siren each time the
zone is shorted. it also flashes (rapidly) the Fire LED, indicating a
problem if the zone is open.

25. Chime only

This zone creates no alarm regardless of the armed state of the
control panel. It chimes anytime it is faulted and displays on the
keypad. Local only.

26. Interior follower delay
2

Instant when the system is armed and no entry or exit delay is being
timed. It is delayed 2 times during entry and exit. It automatically
bypasses if enabled in Segment 1 of Location 23.

27. Interior follower force
armable

Instant when the system is armed and no entry or exit delay is being
timed. It is delay 1 time during entry and exit. It automatically
bypasses if enabled in Segment 1 of Location 23.

28. Entry/exit force
armable delay 2

A trip starts entry delay 2. The lack of a trip during exit delay enables
the automatic bypass or instant mode if programmed.

29. Interior follower with
activity supervision

Instant when the system is armed and no entry or exit delay is being
timed. It is delayed during entry and exit delay times. It sends a report
if the zone activity time is reached without a change of state (refer to
Segment 11 of Location 40). It automatically bypasses if enabled in
Segment 1 of Location 23.

30. Entry/exit with activity
supervision

A trip starts entry delay 1. It sends a report if the zone activity time is
reached without a change of state (refer to Segment 11 of Location
40). The lack of a trip during exit delay enables the automatic bypass
or instant mode if programmed.