Chapter 3: Reporting codes

52

NX-6V2 Control Panel Installation Manual

The siren does not work.

The control panel has a built in siren driver. If the system uses self-contained
sirens instead of speakers, go to Location 37, Segment 2, and turn on bit 1. This
converts the driver output to voltage output.

The interior zones are bypassing themselves.

By default, auto bypass is on in Location 23, Segment 1, bit 3. When this bit is
on, and the panel is armed and an entry zone is not violated during exit time, the
panel assumes that the occupant has not left and bypasses the interior zones to
prevent false alarms. Turn off Location 23, Segment 1, bit 3.

An open zone will not clear.

Take the zone out of all partitions. For example, to delete zone 9:

1. Go to Location 28, Segment 1, and disable any bits that are on.

2. Press * to save.

3. Exit programming.

Cell backup module does not work.

The NX-6V2 can only enroll one bus device other than keypads. If the installation
requires wireless and a cell module, use an NX-148E-RF keypad with a built-in
receiver and the cell module. The panel enrolls the NX-148E-RF as a keypad
rather than a receiver, allowing it to enroll the cell module correctly.