Interlogix NX-6V2 Rev C Installation Manual User Manual

Page 73

Advertising
background image

Appendix B: Reporting codes

NX-6V2 Control Panel Installation Manual

69

Loc. Description

Default

Setting

3 = Aux output to stop timing upon user code

entry

3

3

3

3

4 = Aux output activates only betw een closing and

opening time

4

4

4

4

5 = Aux output activates only betw een opening and

closing time

5

5

5

5

6 = Invert aux output (0 V going to 12 V w hen

activated)

6

6

6

6

47

Auxiliary output 1 event/times

Segment 1 = Event number for output 1

0 (burglary alarm)

Segment 2 = Timing for output 1

10 (seconds)

48

Auxiliary output 2 event/times

Segment 1 = Event number for output 2

1 (fire alarm)

Segment 2 = Timing for output 2

10 (seconds)

49

Auxiliary output 3 event/times

Segment 1 = Event number for output 3

2 (24-hour alarm)

Segment 2 = Timing for output 3

10 (seconds)

50

Auxiliary output 4 event/times

Segment 1 = Event number for output 4

39 (smoke pow er)

Segment 2 = Timing for output 4

0 (follow condition)

51

Autotest control

Segment 1 = Autotest interval

0 = Days

1 = Hours

2 = Days and suppresses the test if any report has

been sent w ithin the last interval

3 = Hours and suppresses the test if any report has

been sent w ithin the last interval

1

Segment 2 = Autotest interval from 1 to 255 days or

hours based on Segment 1

24 (hours)

Segment 3 = Hour of the autotest in 24-hour time

format

2 (0200)

Segment 4 = Autotest report time, min. after the hour.

0

52

Opening/automatic disarm times

Segment 1 = Hour of the opening time

8

Segment 2 = Minutes after the opening time

0

53

Closing/automatic arming times

Segment 1 = Hour of the closing/auto arming time

20

Advertising