Chapter 2: Reporting codes

NX-6V2 Control Panel Installation Manual

45

Segment 3

1. On enables fast loop response (50 mS; off = 500 mS).
2. On enables double end of line tamper zone (mainly used to enable the tamper on wireless
zone.)
3. On enables trouble reporting zone (day zones and fire zones).
4. On if zone type is cross zoned.
5. On enables dialer delay zone (see Location 40).
6. On if zone type is swinger shutdown (see Location 38).
7. On enables restore reporting.
8. On enables listen in (see Location 40).

Segment 4

1. Enables zone activity monitor (see Location 40).
2. On enables end-of-line resistor defeat on zones that are not fire or keyswitch zones.
3. On enables zone to act as request to exit input/disables for alarm activation.
4. On enables zone to act as access entry point. Do not enable this segment unless configured
with access control.
5. On enables zone to act as a door shunt switch.
6, 7, and 8. Reserved.

Segment 5 - Reserved

Note: If dialer delay (Segment 3 Option 5) is turned off, the panel will not send cancel reports
even if enabled in Location 23.

Table 9: Locations 110 to 169

Location

Zone

type

Description

Default

110

1

Alarm code

8

111

1

Feature selection

0, 125, 35678, 0, 0

112

2

Alarm code

2

113

2

Feature selection

2, 125, 78, 0, 0

114

3

Alarm code

7

115

3

Feature selection

5, 1245, 5678, 0, 0

116

4

Alarm code

5

117

4

Feature selection

45, 125, 5678, 0, 0

118

5

Alarm code

5

119

5

Feature selection

457, 125, 5678, 0, 0

120

6

Alarm code

4

121

6

Feature selection

0, 12, 5678, 0, 0

122

7

Alarm code

0

123

7

Feature selection

2, 0, 78, 0, 0

124

8

Alarm code

1