7.11

Step 1. In the Machine Speeds configuration screen turn off the speed limits and program all information

that is known about the stroking speed of the press.

Enter the maximum strokes/minute (enter a number slightly higher than the highest speed
at which the press will be calibrated).

Turn off fixed inch spm by entering 000.
Turn off maximum single spm by entering 000.
Turn off flywheel brake tolerance (unless already known).
Turn off minimum entry by entering 000 (unless already known).
Set option control to recall (001) or not recall (000) speeds.
Turn off Cont. Modes ramp by entering 000.
Set Low spm input offset to 000.
Set Low Output Spm to the lowest speed for this press (this includes the speed at which
the press may be Inched).
Set Low Output Cal. # to 000 (unless already known for this type of drive).
Set Mid Output Spm to 000 until both low and high speeds have been calibrated. This
parameter will typically be used only on eddy current drives and can be set to 000
otherwise.
Set Mid Output Cal. # to 000 (unless already known for this type of drive).
Set the High Output Spm to the highest stroking speed for this press. Once configured the
press control will output 10.00 vdc (cal # 4095) to command this speed.

Note:

If the spm settings and Output Calibration #s are already known for this type of press and
motor drive, these settings can be entered and adjusted if necessary.

Step 2. If very little or no information is known about the speed settings for this type of press, an Output

Calibration mode is provided which should allow the analog output to be manually ramped to the
full speed signal (10.00 vdc) and the drive calibrated to stroke at the correct maximum
strokes/minute. The calibration mode is enabled by moving the cursor onto the parameter Output
Calibration #. The press control will allow entry into this field with the Program/Run switch in the
RUN position so that calibration #s (speed settings) can be entered while the press is stroking in
continuous. Calibration mode begins when a number is entered into this field and ends when this
configuration screen is exited. The calibration number that is entered is converted directly into the
analog output voltage as described in the information below. With a final entry of 4095 (10.00
vdc) the drive can be adjusted to the desired highest stroking speed of the press.

Analog output (vdc) = Calibration # x 10.00

4095

Cal. #

Output vdc

4095

10.00

3890

9.50

3687

9.00

3481

8.50

3276

8.00

3071

7.50

2867

7.00

2662

6.50