4.15

To bypass an output:

1.

The operator must have access control. Access control is described in Section 3. If the user obtains
access control by using the password system, the user must be configured to have access to bypass
the programmable limit switch outputs.

2.

Use the arrow keys to position the cursor onto the desired channel.

3.

If the programmable limit switch channel is currently On, not Bypassed, press the BYPASS ON/OFF
softkey to Bypass the channel.

4.

If the programmable limit switch channel is currently Bypassed, press the BYPASS ON/OFF softkey
to turn the channel ON, not Bypassed.

Section 4.4.2 Change Output

When the user has access control, the CHANGE OUTPUT softkey is used to change the On or Off settings
of the output selected.

To change an output:

1.

The operator must have access control. Access control is described in Section 3. If the user obtains
access control by using the password system, the user must be configured to have access to change
the programmable limit switch setpoints and names.

2.

Use the arrow keys to position the cursor onto the setpoint that is to be changed.

3.

Press the CHANGE NUMBER softkey.

4.

Use the numeric keypad to enter the new data and press ENT.

The softkey selections change according to the setpoint selected. Outputs can be turned on only at a specific
crankshaft angle, but can be turned off either at an angle or after a programmed dwell time. If the cursor is
positioned to an Off setpont, the ENTER ANGLE and ENTER TIME softkeys will appear.

The ENTER ANGLE softkey changes the item to a degrees format and allows an entry from 000 to 359
degrees.

The ENTER TIME softkey changes the item to a time format and allows an entry from 0.01 Sec to 9.99 Sec.
Only outputs 01-04 and 09-12 allow timed off settings, and the second On/Off pair can not be used if the first
is timed off.

Section 4.4.3 Change Name

When the user has access control, the CHANGE NAME softkey allows the user to assign preprogrammed