Retrieving demand reporting information, Table 6-5. sg-di command settings -9 – Basler Electric BE1-851 User Manual

Page 111

Advertising
background image

Figure 6-3. Reporting and Alarms Screen, Demands Tab

Table 6-5. SG-DI Command Settings

Setting

Range

Increment

Unit of

Measure

Default

5 A

1 A

Current Threshold

0 = Disabled

0.5 – 16.0

0 = Disabled

0.1 – 3.2

0.01for 0.1 to 9.99

0.1 for 10.0 to 16.0

Sec. Amps

Pri. Amps

Per U Amps

% Amps

0

Interval

(minutes)

Phase

0 to 60

1

Minutes

15

Neutral

0 to 60

1

Minutes

1

Negative-

Sequence

0 to 60

1

Minutes

1


Example 1.

Make the following demand settings. See Figure 6-3.

Interval Minutes Phase:

15

Interval Minutes Neutral:

1

Interval Minutes Negative-Sequence:

1

Current Threshold (Sec. Amps) Phase:

0.00

Current Threshold (Sec. Amps) Neutral:

5.00

Current Threshold (Sec. Amps) Neg. Seq.:

0.00

Retrieving Demand Reporting Information

Values and time stamps in the demand registers are reported in primary amperes. They can be read at

the front panel HMI and through the communication ports.
Today’s Peak, Yesterday’s Peak, and Peak Since Reset demand values are accessed through HMI

Screen 4.4, DEMAND REPORTS. Demand values viewed at the HMI can be reset by pressing the Reset

key. When the Reset key is pressed, the viewed register value is set to zero and then updated on the
9289900990 Rev R

BE1-851 Reporting and Alarms

6-9

Advertising