Factory Default Logic Settings and Equations for Sensing Input Type H Relays

SL-N=USER

SL-50TP = 1,0

SL-50TN = 1,0

SL-50TQ = 1,0

SL-150TP = 1,0

SL-150TN = 1,0

SL-150TQ = 1,0

SL-51P = 1,0

SL-51N = 1,0

SL-51Q = 1,0

SL-62=0,0,0

SL-162=0,0,0

SL-79 = 0,0,0,0,0

SL-BF = 0,0,0

SL-GROUP = 1,0,0,0,0,/0

SL-43 = 1

SL-143 = 1

SL-243 = 1

SL-343 = 1

SL-101 = 1

SL-VOA = 0

SL-VO1 = VO11

SL-VO2 = 50TPT

SL-VO3 = 51PT

SL-VO4 = 50TNT+50TQT

SL-VO5 = 51NT+51QT

SL-VO6 = 0

SL-VO7 = 0

SL-VO8 = 0

SL-VO9 = 0

SL-VO10 = 0

SL-VO11 = 50TPT+50TNT+50TQT+51PT+51NT+51QT

SL-VO12 = 50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU

SL-VO13 = 0

SL-VO14 = 0

SL-VO15 = 0

Factory Default Logic Settings and Equations for Sensing Input Type G Relays

SL-N=USER

SL-50TP = 1,0

SL-50TN = 1,0

SL-150TP = 1,0

SL-150TN = 1,0

SL-250TN = 1,0

SL-350TN = 1,0

SL-51P = 1,0

SL-51N = 1,0

SL-151N = 1,0

SL-62 = 0,0,0

SL-162 = 0,0,0

SL-79 = 0,0,0,0,0

SL-BF = 0,0,0

SL-GROUP = 1,0,0,0,0,/0

SL-43 = 1

8-8